Inputs

ACCB and transformers

How the ACCB & Transformer card groups each ICR block's inverters onto combiner boxes and transformer forms, and sizes the power transformer.

The ACCB & Transformer card, the second card on the Electrical tab, holds the rules that group the plant's AC equipment. Inside every ICR block — one inverter control room and the tables wired to it — it gathers the string inverters onto AC combiner boxes (ACCBs) and the combiner boxes onto inverter duty transformers (IDTs), and it sizes the power transformer at the main control room for the plant as a whole. The counts, the transformer loads and the ratings it produces are the ones the Summary view, the Workings view, the bill of materials, the single-line diagram and the deliverables all print, so they agree with one another.

The card changes with the inverter topology chosen at launch. In a central-inverter design it is titled Transformer: there are no combiner boxes, and the central inverters in each control room land on the transformers directly. See Choosing a design mode.

The ACCB & Transformer card at its defaults: inverters per ACCB, the transformer forms 5, 3 and 2 windings, the transformer size limit, the standard transformer ratings as chips, MV voltage, the power transformer margin, derating and ratings, the LV voltage waiting for the OND file, and the line Now: Generate a layout first.
The ACCB & Transformer card

The fields

Top to bottom, as the card shows them. Every row except the last two is yours to set.

FieldDefaultRangeWhat it does
Inverters per ACCB, max (string design)151–60The most string inverters on one AC combiner box. Each ICR block gets its own ACCBs, with the inverters shared evenly between them
Transformer forms (windings)5, 3, 2whole numbers 2–13The transformer forms this project allows, by total windings: 5 is one MV winding and four ACCBs or central inverters. Each ICR takes the largest form first, every transformer full
Transformer size limit17.2 MVA0.5–100.0 MVAThe largest transformer allowed. A block whose load is bigger gets more transformers. Never above the largest listed rating
Standard transformer ratings (kVA)2,500, 3,150, 5,000, 6,300, 8,000, 10,000, 12,500, 16,000positiveThe ratings an inverter duty transformer can take. Each transformer takes the smallest one at or above its load
MV voltage33.0 kV0.4–400.0 kVThe transformers' medium-voltage side, and the MV cables to the main control room
Power transformer margin1.00 ×1.00–3.00 ×Multiplies the plant's maximum AC output when the power transformer is sized
Power transformer derating1.00 ×0.50–1.00 ×Divides it. Set below 1.00 for a site above about 40 °C ambient or 1,000 m altitude, so the same load needs a higher rating
Standard power transformer ratings (MVA)10, 12.5, 16, 20, 25, 31.5, 40, 50, 63, 80, 100positiveThe ratings the power transformer can take. Above the largest, as many transformers as the need requires
LV voltageneeds the OND fileread-onlyThe transformers' low-voltage side, read from the inverter file
(the answer line)Now: Generate a layout firstread-onlyWhat the rules produce for the current layout

The margin and the derating move in steps of 0.05. At the defaults the line under Transformer size limit reads Capped at 16,000 kVA, the largest listed rating.

Editing a list

The forms and the two rating lists are lists of chips. Type in the Add… box and press Enter; a pasted list goes in at once. Commas, semicolons and spaces separate values, so 16,000 is one size and 4000,20000 is two. A chip's × removes it, except the last one, which stays. A changed list shows a Reset to standard link.

What cannot go in stays as you typed it, with the reason beside it, and the list keeps what it had:

EnteredReason
A word or symbol“x” is not a number.
Zero or a negative figurex is not a positive rating.
A form outside the rangex windings is outside 2–13 windings.
A value the list already holdsx is already listed.

The LV voltage line

The low-voltage side is not an input. It reads needs the OND file until an inverter file is loaded on the inverter card, then the file's output voltage, for example 800 V · from the OND, or not in the OND file when the file does not declare one. See Inverter settings.

The answer line

The last line of the card, prefixed Now:, shows what the rules produce for the layout on screen, and updates as you change them.

StateWhat the line reads
No layout yetNow: Generate a layout first
String design, inverter file loadedNow: 12 ACCBs · 8 transformers: 4 × 5,000 + 1 × 8,000 + 3 × 10,000 kVA
No inverter fileNow: 12 ACCBs · 4 transformers · ratings need the OND file
Central designNow: 16 central inverters · 4 transformers: …, or … · ratings need the OND file
A transformer's load fits no listed rating within the limitthe ratings, then · 1 with no listed rating (the count of such transformers). The line's tooltip lists each one, such as ICR-3's transformer load 17,100 kVA fits no listed rating
The ACCB & Transformer card after a layout with an inverter file: LV voltage 800 V from the OND and the answer line Now: 12 ACCBs · 5 transformers: 4 × 10,000 + 1 × 16,000 kVA.
The card after a layout

The answer line covers the ACCBs and the inverter duty transformers only. The power transformer's figure is in the Summary view and the bill of materials.

How a block is grouped

The grouping is made per ICR block: one inverter control room and the tables wired to it through their inverters or string monitoring boxes (SMBs). No combiner box and no transformer is shared between two blocks. See ICR blocks.

For each block:

QuantityRule
ACCBs (string design)The block's inverters ÷ Inverters per ACCB, max, rounded up. The inverters are shared out in order, so that no two ACCBs differ by more than one inverter
Central inverters (central design)The block's SMBs ÷ Max SMB per Central Inverter, rounded up, at least one, with no limit per control room. After a Simulation with AC capacity the count comes from the plant AC instead; see Inverter settings
TransformersThe feeders (ACCBs or central inverters) go onto the largest form first, every transformer full. A count the forms cannot cover exactly backs off larger forms first. With no exact cover, the cover with the fewest spare windings is used, the spare on the last transformer
The limitWhile any transformer's load is over the limit, the largest form is dropped for that block and the feeders are filled again. The smallest form is kept whatever the limit
Which limitTransformer size limit, but never above the largest listed rating. With the defaults that is 16,000 kVA, not 17.2 MVA
Transformer loadThe inverter file's maximum AC output over every inverter or central inverter on that transformer. A file with no maximum uses its nominal output
Transformer ratingThe smallest listed rating at or above the load and no larger than the limit. When none fits, the transformer has no rating and is counted as with no listed rating
WindingsThe form. One winding is MV; the others carry a feeder each, or stand spare
VoltagesLow voltage from the inverter file; medium voltage from MV voltage

A spare winding is reported by the design check E-15 Transformer forms, for example ICR 2: 3 ACCBs on a 5-winding transformer, 1 LV winding spare. Add a 4-winding form or change the block. See Design checks.

How the feeders fill the default forms

With forms 5, 3 and 2:

FeedersTransformers (feeders on each, its windings)
11 on a 2-winding
22 on a 3-winding
32 on a 3-winding, 1 on a 2-winding
44 on a 5-winding
54 on a 5-winding, 1 on a 2-winding
64 on a 5-winding, 2 on a 3-winding
74 on a 5-winding, 2 on a 3-winding, 1 on a 2-winding
84 on a 5-winding, twice
104 on a 5-winding, twice, then 2 on a 3-winding

The list decides what is possible. With forms 5 and 3, seven feeders take a 5-winding and a 5-winding with three feeders, one winding spare. With forms 5 and 4, six feeders take two 4-winding transformers. With the 5-winding form alone, three feeders take one 5-winding, with one winding spare.

A worked example

A string-design block, the card at its defaults, and an inverter file giving 300 kVA maximum output per inverter:

InvertersACCBsLargest form's loadResult
604 of 1560 × 300 = 18,000 kVA on a 5-winding, over 16,000The 5-winding is left out. Two 3-winding transformers, 2 ACCBs and 9,000 kVA each, rated 10,000 kVA
53453 × 300 = 15,900 kVA on a 5-windingOne 5-winding transformer, rated 16,000 kVA
413, of 14, 14 and 13No 5-winding: three feeders fill a 3-winding and a 2-windingA 3-winding carrying 2 ACCBs and 8,400 kVA, rated 10,000 kVA, and a 2-winding carrying 1 ACCB and 3,900 kVA, rated 5,000 kVA

The Transformers (IDT) row of the Workings view names the forms, the limit, the ratings and any form left out, for example 5-winding left out, over 16,000 kVA full. See The Workings view.

Without an inverter file

With no inverter file loaded the card still groups — the ACCB, central inverter and transformer counts are made — but there is no load, so the transformers carry no rating and no low-voltage figure. The Summary view says so, 4 · rating needs an OND file, as a link to the file row. Load the inverter file on the inverter card to fill them in.

The power transformer

The power transformer steps the whole plant's output up at the main control room. It is sized only when three things are true: a plot holds a main control room, an inverter file is loaded, and the plant has been grouped. Place the main control room from the Tools tab — see Site equipment. With the grid connection by others it is left out.

It is sized from every inverter in the plant (every central inverter, in a central-inverter design), including the plots that feed the main control room through their own unit substation:

Add up the maximum AC output

Every inverter at the inverter file's maximum AC output, in MVA.

Apply the margin and the derating

Multiply by Power transformer margin and divide by Power transformer derating. The result is the plant's need.

Pick the ratings

If the need fits under the largest listed rating, one transformer takes the smallest listed rating at or above it. If not, the need is split across as many transformers as the largest rating requires, each taking the smallest listed rating at or above its share.

The Summary view's Power transformer (MVA) row carries the result, or the reason there is none: needs an OND file, needs an MCR on the layout or by others. The basis reads, for example, Σ PMaxOut 58.1 MVA × margin 1 ÷ derating 1 = 58.1 MVA → next listed rating, which with the default ratings gives 63.

The margin ships at 1.00. Rounding up to the next listed rating already leaves headroom; raise the margin only when your own practice asks for more.

What changing the card does

The card acts on the layout already on screen. You do not generate again.

  • Every change regroups every plot at once. Nothing moves: no table, inverter or cable is placed or routed again. Before the first layout a change waits, and the next Generate Layout groups the plant with it.
  • The answer line and the Summary view refresh straight away. The earthing layer redraws if it is on, and an open Earthing Design window closes.
  • The layout does not go out of date. The card's fields are not layout inputs, so no amber marks appear. Loading an inverter file is different: it regroups in the same way, but it does mark the layout out of date, because the inverter file is an input to the run. See Out-of-date results.
  • The bill of materials recounts the next time you open the BOM view. Your edits to it are kept. See Bill of materials.
  • An automatic single-line diagram you have not touched rebuilds at once. One you have edited is kept and marked out of date, with a choice to rebuild it or keep it. See Building a diagram from the plant.

The card's rules are saved in the project file and come back when it is reopened; the grouping itself returns with the saved layout, so nothing is regrouped on opening. See Projects.

Where the grouping appears

Every output reads the same grouping, so a count in one agrees with the count in the others.

WhereWhat it shows
Summary view, Plant sheetACCBs (string design), Transformers (IDT) — such as 4 × 16,000 kVA, 2 × 12,500 + 2 × 16,000 kVA, 4 · rating needs an OND file or 4 · 1 with no listed rating — and Power transformer (MVA). See Summary view
Summary view, By block sheetACCBs or Central inverters, Transformers (IDT) such as 2 × 12,500 kVA, and Transformer load (kVA) such as 13,200 · 83 %, for each block
Workings viewHow the transformers and the power transformer were reached
Bill of materialsAC combiner box (ACCB), Inverter duty transformer and Power transformer, with remarks that follow the card. See Bill of materials
Single-line diagramThe automatic build's ACCB and transformer counts, ratings, windings and voltages. See Building a diagram from the plant
DeliverablesThe automatic single-line diagram in the drawing set, and the ACCBs, transformers and feeders in the schedules workbook

MV voltage

MV voltage is printed wherever a transformer's voltages are, and the MV cables are sized at it too, so their sizes and drops in the schedules follow this card.

Where to go next