Exports

The drawing set

The package's numbered sheets - cover, general arrangement, block, pile, earthing and single-line sheets - and the DXF twin that holds them in CAD.

The drawing set is the package's construction-style drawings: numbered sheets with a title block, written as one PDF with a bookmark per sheet, and as a DXF with one paper layout per sheet. It is the Drawing set and Drawing set (DXF) rows in Export deliverables.

Sheets run in the order D0, D1, D2, D4, D6, D5, numbered through the set. A bookmark reads "4 · D2 · Block B01 — layout".

SeriesWhat it isSheetsPaper and scale
D0Cover and drawing register1A3, no scale
D1General arrangement1, plus a panel continued sheet when the panel overflowsA1, or A0 when A1 would need 1:10000 or smaller; the continuation A3, As shown
D2Block layoutOne per ICR block, split into tiles when a block is largeA3, one scale for the set
D4Pile layoutTypical pile pattern, then one per D2 tileA3
D6Earthing layoutOne per D2 tileA3
D5Single line diagramThe plant overview, then a typical block per kindA3, A1 or A0 by the ICR count, not to scale

When a series is left out

A series that can't be drawn is left out, and D0 says so. For example: "Not in this set: D4, Pile layout. Piles are placed from the pile pattern, and none is defined." The other reasons read "No table has piles.", "The plant has no ICR blocks." and "The snapshot has no earthing design."

The title block

Every sheet carries one: company, logo and address; project, client and location; drawing title and number; revision and status; scale, size and sheet, such as "1 of 13"; drawn, checked and approved; the date; the basis, which names the snapshot and the source file; the coordinate system; and "Prepared with SolarLayout".

A draft prints REV — and STATUS DRAFT. An issue prints its revision and FOR REVIEW, FOR APPROVAL or FOR CONSTRUCTION. See Issuing a revision. The company, its logo and the numbering come from Company.

D0, cover and drawing register

The first sheet says what the set is. It holds the project, client and developer; the location with its coordinates; the coordinate system and how the location is known (from the survey coordinates, placed by the user or location not known); the MWp DC, MW inverter AC and DC : AC headlines; the status band; the revision history; what is in the package; a site key plan; and the register of every sheet with its drawing number, title, size and scale.

A draft's band reads "Draft · not issued" and "Not for construction." An issue's reads "FOR REVIEW" and "Issued 5 Nov 2026 by AC."

D1, general arrangement

"General arrangement — all blocks" shows the whole plant at a stated scale. Its panel holds the block schedule, a DESIGN BASIS box that points to section 3 of the design report, the ELECTRICAL CHAIN from string to grid, up to three typical details and lettered notes.

The notes say what the sheet leaves out: "Not on this sheet: table IDs, inverter tags, DC routes, piles and arrester protection circles."

The general arrangement sheet: the whole plant at scale in its grid, every block labelled with its capacity, and below it the summary, block schedule, legend and notes beside the title block.
The general arrangement

D2, block layout

One sheet per ICR block at one scale for the whole set, each with the block's data and a key plan. Tables carry their IDs, or row ranges where the IDs are too small to print, and the sheet shows inverter zones. A large block splits into tiles with match lines: "Block P2-B01 — layout · tile 1 of 2".

"Not on this sheet: piles, DC string routes and cable sizes (see the cable schedule)." Sizes are in the schedules workbook.

A block layout sheet: one block's tables with their IDs, inverters and ICR, neighbouring blocks greyed, and a panel of block data, key plan, legend and notes above the title block.
A block sheet

D4, pile layout

Drawn whenever a pile pattern is defined, whatever the Piles overlay on the plot says.

The Typical pile pattern sheet dimensions the pattern at 1:150, for full and half units, with its PILE DATA.

The typical pile pattern sheet: one table's piles numbered and dimensioned along their overhangs and spans, with the pile data, legend, notes and title block on the right.
The typical pile pattern

The block sheets follow the D2 tiles. Each draws a dot per pile and lists the setting-out points SP1, SP2 and SP3 with their pile ID, easting, northing, latitude and longitude. For every pile's coordinates, use piles.csv, which is written beside the drawings.

A block pile layout sheet: the block's tables with their piles, and a panel of pile data, the setting-out points with their coordinates, key plan, legend and notes.
A block's pile layout

D6, earthing layout

Drawn from the project's earthing design, one sheet per D2 tile. The panel gives the block's earthing strip in metres, its earth pits and conductors, the earth grid (IEC Ω against the target) and the earth grid check, with a legend by duty. While soil resistivity is unmeasured the sheet says "Soil resistivity not measured: checked once a value is entered".

A block earthing layout sheet: the block's tables with the earth strips and pits drawn over them, and a panel of earthing data, key plan, legend and notes.
A block's earthing layout

D5, single line diagram

The automatic diagram, from the grid to each ICR's PV array, with a rating on every device. "Single line diagram — plant overview" comes first, then a typical block A, B and so on, one for each kind of block. Tables that overflow get sheets of their own.

Where a value isn't in the design the sheet prints "Not designed" or "by others": "A rating marked Not designed needs the inverter's datasheet."

The plant overview sheet of the single line diagram: from the grid and power transformer down each ICR's transformers, ACCBs and string inverters to its PV array, with a panel of plant figures, symbols and notes.
The single line diagram sheet

D5 is always the automatic diagram. A diagram you edited or traced in the SLD view does not reach the package, and the package doesn't wait for it. It leaves through PDF… or DWG… on the SLD view's Export card. See Exporting the diagram.

The DXF twin

The DXF holds the same set for a CAD user. It is written in R2010 format, in metres, with Arial text.

  • Model space holds the design once, in the drawing's own coordinates: UTM for a KMZ site or a drawing located by its own coordinates, and the source drawing's coordinates for a CAD or image boundary placed by hand or continued as layout only, so it overlays that drawing.
  • There is one paper layout per sheet, named by its drawing number. Viewports are at the sheet's scale, with the layers that sheet doesn't draw frozen.
  • Sheets name grayscale.ctb as their plot style.
  • When the site is located, the file carries its geographic location.
  • Writing the same snapshot on the same date gives the same file, byte for byte.
The model space of the drawing set's DXF drawn from its layers: the boundary and road, water and exclusions, every table, the buildings and devices, and the arresters with their circles.
The drawing set's DXF

Layers

Layers use standard names, and a layer is written only when something uses it. Among them:

LayerHolds
C-SITE-BNDYThe site boundary
C-ROAD-PERIThe perimeter road
C-SITE-EXCL-OBST, C-SITE-EXCL-TLCR, C-SITE-EXCL-WATRExclusions: obstacles, transmission-line corridors, water
C-BLDGBuildings
E-PV-TABLTables
E-PV-ZONEInverter zones
E-INVRInverters
E-IDTInverter-duty transformers
E-ERTH-*The earthing design, with every pit's position
E-SLD-*The single-line diagram
G-ANNO-*Annotation
G-BLCK-…Blocks

Blocks and attributes

ObjectIn the file
TablesBlocks without attributes, one per table shape, such as PV-TABLE-32180x4728. Table IDs are not written
DevicesBlocks with ID, block, strings and kWp as attributes
BuildingsCarry their ID
PilesA pattern block per table type
Title blockOne attribute block on each sheet

What the twin leaves out

The twin holds the design, not your drawing marks. Cable routes you drew by hand are in it. Sketch annotations, dimensions and layers you made, street lights and terrain contours are not. It carries no logo: the company's name prints instead.

The earthing drawing on its own

Export ▾ ▸ Earthing layout (DXF)… writes the earthing plan as a separate drawing, without writing a package. Export DXF… in the Earthing Design window does the same from there. See Earthing design.

Where to go next

On this page