Inputs

Inverter settings

Strings per inverter or SMB, the DC harness and fuses, communication and weather stations, and what a manufacturer inverter file changes.

The inverter card on the Electrical tab sets how the plant's DC output is collected and converted, how much of it one piece of collection equipment takes, how the strings reach it and how the devices report, and which manufacturer's machine the AC side is sized from. Its title and its fields follow the inverter topology you chose at launch, because the two topologies collect the strings in different places. See Choosing a design mode for the choice itself.

The Electrical tab carries three cards, in this order: this inverter card; the ACCB & Transformer card — titled Transformer in a central-inverter design — which groups the inverters onto combiner boxes and transformers, see ACCB and transformers; and the Cables card, which decides whether the cables are routed and how they are laid, see Cables.

The Electrical tab's three cards in one tall image: String Inverter, ACCB & Transformer and Cables, at their defaults.
The Electrical tab, top to bottom

One definition governs everything on this page. A string is one row of modules within an MMS-Table (MMS — module mounting structure). A fixed-tilt table configured with two rows therefore carries two strings. A half table holds whole strings only, half as many as a full table, rounded down. Everything you set here is counted in strings, so the table configuration and this card are two ends of the same decision — see Table configuration.

The card in each design

Inverter topologyCard titleWhere the strings are collected
String inverterString InverterString inverters distributed across the plant, each converting DC to AC where it stands and sending AC onward
Central inverterSMB – String Monitoring BoxString monitoring boxes distributed across the plant, each collecting strings and passing DC onward

In a central-inverter design the string monitoring box — SMB — is the collection point. It does no conversion: it gathers the strings assigned to it and sends their combined DC output on to a central inverter, which sits inside an ICR (inverter control room) rather than out in the field.

The String Inverter card at its defaults: maximum strings per inverter, DC harness, String fuses inline at the connector, Communication over the AC cable, Weather stations at the MCR, and the OND file row with Load .OND and View.
The String Inverter card
FieldDefaultRangeWhat it does
Max strings per inverter201–500The largest number of strings one string inverter accepts
DC harnessOne string per inputor Y, two strings per inputHow the strings reach the inverter's inputs
String fusesInline, at the connectorfour optionsWhere the string fuses sit
CommunicationPower-line, over the AC cableor RS485, daisy-chainedHow the inverters talk to their control room
Weather stationsAt the MCRthree optionsWhere the weather stations stand
OND (inverter)No OND file loaded—Load .OND reads a PVsyst inverter file; View opens it once loaded

These fields are inputs to the run and are saved with the project. A change takes effect at the next Generate Layout, and marks the layout out of date until then.

Maximum strings per inverter

The first field caps how many strings one collection point is allowed to take. The application clusters the placed tables and puts down as many inverters or monitoring boxes as the cap requires, so a lower number means more equipment, each covering a smaller group of tables.

The count works from the fillable cap, the highest load at or under your maximum that whole tables can reach. On two-string tables with no half tables, a maximum of 23 acts as 22, because 23 strings cannot be made from whole tables:

devices = plant kWp ÷ (fillable cap × string kWp), rounded up

At 54,280 kWp and 341.6 kWp a device, that is 159 inverters. Set the maximum from the inverter or monitoring box you intend to buy, counted the way the application counts: one string per row of modules in a table. The number of modules in that row does not enter into it. What the row holds decides the string's voltage and current, which is a separate question, settled by string sizing.

The unit count and the DC load on each unit are reported in the Summary view's Electrical group: String inverters and Largest DC load per inverter (kWp) in a string design, SMBs and Largest DC load per SMB (kWp) in a central design. See Summary view.

DC harness and string fuses

DC harness decides whether each string has its own home run.

OptionWhat it does
One string per inputEvery string has its own cable to its own inverter or SMB input
Y, two strings per inputTwo strings share one cable from the Y to the device, so that cable is halved. Each string's own cable before the Y, along the table or tracker, stays its own

With a Y, two strings of a table share a Y and an odd one runs alone. Tables with one string — a one-row table, a one-string tracker, a half unit — share a Y with a neighbour on the same device: along the row first, then the next row. The DC cable splits accordingly: the part before the Y at String cable size, the shared part at Y pair cable size, both in Advanced settings.

String fuses decides where the fuses go. The field names the device in its options:

OptionDefault for
Inline, at the connectorA string-inverter plant
Inside the inverter or Inside the SMBA central-inverter plant
Inline and inside the inverter or Inline and inside the SMBA central-inverter plant with a Y
None—

The field follows the harness while it sits at the harness's default. An option you choose yourself stays.

Both reach the bill of materials:

HarnessFusesConnector line
One string per inputAnyDC connector, male and female, 1 per string plus spare
One string per inputInline, or inline and insideAlso DC connector set with inline fuse
YInline, or inline and insideY connector set with fused arms, 1 per pair
YInside the device, or noneY connector set, 1 per pair

The fuse sizes themselves are worked out from the module's short-circuit current and Max series fuse — see Module specifications and Bill of materials.

Communication and weather stations

Communication sets how the devices talk to their control room.

OptionWhat it does
Power-line, over the AC cableThe default on a string-inverter plant. The BOM carries a SACU and a PLC box per ICR
RS485, daisy-chainedFixed on a central-inverter plant. The devices are grouped round each ICR into chains, as few as keep within RS485: devices per chain (20) and RS485: chain length (1,200 m), both in Advanced settings. The chains are counted, not drawn

A device farther from its ICR than the chain length gets an over-limit chain of its own, and the BOM line says so. Every ICR with an MV run also gets optical fibre as long as that run, in conduit, so no fibre is counted without a main control room, a unit substation or a handover point.

Weather stations sets where they stand.

OptionWhat it does
At the MCRA station at the main control room
At the MCR, module sensors at every ICRThe same, with a module-temperature sensor station at each ICR
NoneNo stations

With the grid connection by others the first two read On site and On site, module sensors at every ICR.

Maximum SMBs per central inverter

Central-inverter design only. This field and Max strings per SMB multiply out to the capacity of a central inverter:

Central inverter capacity = SMB capacity × Max SMB per Central Inverter

The central inverters are counted per ICR block — one control room and the monitoring boxes wired to it. Each block gets its SMBs ÷ Max SMB per Central Inverter, rounded up, and at least one, with no limit per building. Blocks of 39, 35, 40 and 45 SMBs at a maximum of 2 take 20, 18, 20 and 23 central inverters. The control rooms themselves are sized and placed from the ICR Block capacity on the Site tab, not from this card — see Control rooms.

Summary rows Central inverters and DC limit per central inverter (kWp) report the result, the second being SMB kWp × this field.

After a simulation with AC capacity

A Simulation with AC capacity on a central plant sets the count from the plant's AC instead: the AC capacity ÷ the inverter's rated AC, rounded up, exactly. The inverters are split with full ICRs first and the rest in the last, the largest counts going to the ICRs with most SMBs, each ICR with at least one and no more inverters than SMBs. The SMBs are shared evenly over each ICR's inverters.

While that count applies, Max SMB per Central Inverter is greyed out, with the hint Set by the AC simulation: the busiest inverter's SMBs. The inverter count comes from the plant AC. An inverter over the study's overload limit is reported by design check E-14; it never adds an inverter.

Loading a manufacturer inverter file

The card's file row reads No OND file loaded beside Load .OND and View. Click Load .OND and, in the Load Inverter OND File dialog, pick the .OND file — the PVsyst inverter file the manufacturer publishes for the machine you intend to buy. The row then shows the manufacturer and model, and View becomes available.

The String Inverter card after an inverter file is loaded, with the make and model on the OND row and View enabled.
Inverter file loaded

The file settles the AC side of the design:

  • The file's AC rating sets the plant AC capacity. The application takes the nominal AC power of one machine from the file, or its maximum when the nominal is missing, and multiplies it by the inverter count. The result is the Summary view's Plant AC capacity (MWac), unless an AC-capacity study set the target. Inverter AC rating (kW) gives the one machine's figure.
  • The DC / AC ratio follows. DC / AC ratio is the DC capacity ÷ the plant AC. Without an inverter file there is nothing to divide by, and the rows read needs an OND file. After a study, when the installed machines differ from the target, two further rows show the installed figures: Inverter AC capacity (MW) and DC / AC on inverters.
  • The transformers are sized from it. The file's maximum AC output, summed over the inverters on each transformer, is the transformer's load and decides its rating, and summed over the plant it sizes the power transformer at the main control room. The file's output voltage becomes the transformers' low-voltage side, shown on the next card's LV voltage line. Without the file the grouping is counts only, and the card's answer line ends ratings need the OND file. See ACCB and transformers.
  • The AC feeders are sized from it. Each inverter-to-ACCB feeder carries the file's maximum AC current. See Cables.

Without the file the bill of materials' Capacity line reads AC not designed: the AC rating comes from the inverter's OND file, and the string inverter and transformer lines read Needs design input.

Each Generate and each loaded file stamps the machine's make, model and ratings on the design. The deliverables name it as <make> <model> (<power> kW), or Inverter (not from a datasheet) with no file, which design check C-04 reports.

Loading an inverter file on a layout that already exists regroups the plant at once, and marks the layout out of date, because the inverter file is an input to the run. See Out-of-date results.

The file's location is saved in the project. If the file has moved or gone when the project is reopened, the row reads Not found: and the file name, or Could not load: for a file it cannot read, and the layout opens out of date.

Loading an inverter file does not set the inverter efficiency used in the energy calculation. The String / Central Inverter efficiency field on the Yield tab stays at whatever you entered; read the file's efficiency curve (below) and set that field yourself. See Loss assumptions.

Viewing what was read

View opens the file read-only in a window titled Inverter (OND) followed by the file name, laid out the way PVsyst presents it, so you can confirm the machine before designing around it. It has five tabs: Main parameters, Efficiency curve, Additional parameters, Output parameters and Sizes and technology.

The Inverter (OND) viewer on its Main parameters tab with the tab strip visible.
The inverter file viewer

The Efficiency curve tab draws efficiency against load from the points in the file. Read it against the inverter loading your DC / AC ratio implies: a plant run at a high ratio spends most of its hours in the upper part of that curve, and the conversion loss you enter in the yield calculation should agree with what the curve shows there.

The Efficiency curve tab of the inverter file viewer.
The inverter efficiency curve

The file is also what makes string sizing possible

The number of modules you may wire in series is bounded by the inverter's tracking voltage window — the range of DC voltage over which the inverter can hold the maximum power point (MPPT — maximum power point tracking). That window is a property of the machine, and the application reads it from the inverter file. With no inverter file loaded there is no window, and therefore nothing to size a string against: the Size… button on the Array tab asks for one before it opens the calculator.

This is why the module file and the inverter file are usually loaded together at the start of a session. Both are also required by the Simulation with AC capacity study, which sizes the plant backwards from a target AC figure using the same two files.

Where to go next

On this page