Layout

Lightning arresters

How arresters are placed on a coverage grid, the ground each mast keeps clear, the settings behind them, and where they show up.

An LA — lightning arrester — is a mast that protects a circular area of ground around it against a direct strike. When you ask for them, the application places masts across the plant on a grid sized so that every table and building falls inside at least one protected circle, then removes the tables and trackers the mast's pile or its shadow touches.

Arresters are off by default. Nothing about the layout changes until you tick them on, and turning them on reduces capacity on a fixed-tilt plant and on a tracker plant alike, which is why the decision belongs to you rather than to a default. The rules are the same for both mountings.

Turning arresters on

Both settings live on the Site Parameters card of the Site tab. They are read when you click Generate Layout; arresters are placed late in the run, after the module tables and the inverter control rooms are down and before the inverters and cables.

FieldDefaultRangeWhat it does
Place Lightning Arrestersoff—Turns arrester placement on for the run. The radius field below stays greyed out until this is ticked.
LA protection radius100.010.0–500.0The radius, in metres, of the circle a single arrester protects. The grid the masts start from is spaced at 1.4 times this.
The Site Parameters card with Place Lightning Arresters ticked and the LA protection radius enabled at 100 m.
Lightning arresters switched on

See Site parameters for the rest of that card. Both the tick and the radius are kept in a project file.

What happens when arresters are off

No arresters are placed, no ground is reserved for them, and module tables fill the whole usable area — the plant boundary shrunk inward by the perimeter road width, with obstructions and terrain exclusions subtracted. The Summary view has no Lightning arresters row and the Lightning arresters chip does not appear under the view.

The design check C-02 Lightning protection designed fails until arresters are placed. See Design checks.

How the masts are placed

Four steps, in this order, on every run with the option on.

Lay the grid

Grid positions are laid out on a square grid centred on the usable area, with a spacing of 1.4 times the protection radius: 140 m at the default 100 m.

The worst-served point in a grid square is its centre. At this spacing that point is the spacing ÷ √2 from the masts around it, or 0.99 of the radius, so the circles just cover the square with a little to spare.

Move each position into a gap

A mast stands in the ground between structures, not on one. On a fixed-tilt plant each position moves north or south to the nearest gap between rows. On a tracker plant it moves east or west to the nearest gap between columns.

The moved position is kept only if it lies inside the usable area, so a mast is never placed on the perimeter road, in a water body, inside a line corridor or on excluded ground. Two positions that land on the same spot count once. The result is regular across the middle of the plant and ragged wherever the boundary or an obstruction cuts into it.

Complete the coverage

Dropping positions at the edges would leave outlying equipment unprotected, so a second pass measures every table, ICR, main control room and unit substation against the masts already placed. Anything whose centre is farther than the radius from every mast gets one more, in the nearest gap.

On a long, thin or awkwardly notched site this pass adds the masts the regular grid could not reach, and those are the ones you will see off the grid lines.

Clear the keep-clear

Every table or tracker unit touched by a mast's pile, or by its shadow, is removed. The next section covers what that means.

The Layout view with the Arrester coverage layer on: a shaded protection circle around each mast, overlapping across the whole plant.
Arrester coverage

The keep-clear, and what it costs

The circle is the protection. The keep-clear is the ground the mast itself takes from the plant, and it has two parts:

  • The pile. A square of the LA pile Ø, and never less than 0.2 m.
  • The shadow. The mast's shadow swept over the Shadow Window on every day of the year. It reaches further the taller the mast and the wider the window.

A table or a tracker unit touched by either is removed whole. The plant's module count and DC capacity are recomputed from what survives, and the land account books the ground as arrester keep-clear. Without a known latitude, or with the height at 0, only the pile clears.

A zoomed plot with one arrester mast and its hatched keep-clear shape in the ground cleared of tables, close to the fence and a string inverter.
A mast's keep-clear

To see the figure for your own site, generate once without arresters and once with them and compare the DC capacity (MWp) row of the Summary view. On the bundled sample site at the defaults, a fixed-tilt plant of 54.28 MWp and 1,589 tables takes 26 masts, 17 from the grid and 9 from the coverage pass, and they remove 89 tables, or 3.04 MWp. The Lightning arresters row of the Workings view gives the count and capacity removed on your own plant.

On a tracker plant the masts stand in the gaps between columns, and the same rule removes any unit a pile or shadow touches.

A zoomed tracker layout with small arrester masts and their labels in the gaps cleared between tracker columns.
Arresters on a tracker plant

Arresters clear tables, so a capacity comparison between two designs is not like-for-like unless arresters are set the same way in both runs.

The settings behind the keep-clear

Two further arrester fields sit on the Structures & Shadow (keep-clear) card of the Site tab, alongside the building footprints:

FieldDefaultRangeUnitWhat it does
LA height9.00.0–100.0mSets the mast's shadow, and prints in the arrester's line of the bill of materials. At 0 the mast casts no shadow
LA pile Ø0.300.0–5.0mSets the mast's footprint on the ground

The Shadow Window on the same card, 9.0 to 15.0 solar hours by default, sets the span of each day the shadow is swept over. Changing any of these fields marks the layout out of date until you generate again. See Structures and shadow.

Raising or lowering the protection radius

The radius sizes the protected circle and spaces the grid, so changing it changes the mast count more than you might expect.

ChangeMasts placedTables removed
Raise the radiusFewerFewer
Lower the radiusMoreMore

Two things to hold in mind:

  • The grid spacing follows the radius in both directions, so the number of positions changes with the area of a grid square, not with its side. Doubling the radius gives about a quarter of the grid positions.
  • The radius is a claim about the mast you will build. Raising it to thin out the grid only reduces cost if the installed arrester genuinely protects that far. The application takes the number you give it and does not check it against a protection standard.

Reading arresters on the plot and in the outputs

  • On the plot. The masts and their LA-n labels draw with the Plant layout row of the Layers ▾ popover. Arrester coverage, off by default, adds the protection circles in orange-red. Shadows (keep-clear), off by default, shows the ground kept clear. See Views for the popover.
  • In the Summary view. The Lightning arresters row is in the Electrical group when the design has arresters, with a Total column on a multi-plot site, and the Lightning arresters chip under every view appears once some are placed. Because arresters are placed after the tables, the module and capacity rows already account for the tables they removed.
  • In the design checks. C-02 Lightning protection designed reads whether they are placed, and E-09 Tables inside arrester cover counts any table left outside a circle against a limit of 0 tables, which you can change in Advanced settings.
  • In the bill of materials. The arrester's line carries the mast height. See Bill of materials.
  • In the KMZ. Arresters are labelled points in a folder of their own, with the protection radii hidden. See Schedules and KMZ.

Arresters and cleaning robots

A mast's keep-clear interrupts the run of tables a cleaning robot drives along. The robot sizing tool lists every gap too wide for a standard bridge between tables, and separates the gaps at equipment from the others, so you can decide which to bridge. See Robotic module cleaning.

Earthing the arresters

The earth pits under each arrester are sized in Earthing Design (on the Tools menu and in the Studies card), not here. It gives every arrester a ring of at least Pits per LA earth pits, and adds pits until the ring meets the LA earth pit target, 10 Ω by default, following IEC 62305-3 (type A arrangement). Its bill of quantities carries a test joint for each arrester. See Earthing design.

An arrester placed by hand

Sketch Mode's ➕ LA tool, in the PLANT OBJECTS group, stands a mast at the point you click, not moved to a gap, and removes the tables under its pile and shadow. See Sketch Mode.

The plant's arrester design comes from Place Lightning Arresters and Generate Layout: the grid, the coverage pass and the checks above all work from it. To change how many masts the plant carries and where they fall, change the radius and generate again.

Where to go next

On this page