Bill of materials

Line reference

Every entry in the built-in BOM profile, by category, with its unit, how it is counted and when it applies, and what feeds the quantities.

This page lists every entry in SolarLayout standard, the built-in BOM profile, in the order of the BOM view. An entry gives a line when it applies to your design and the layout has something to count. A company or client profile starts from this list and changes or adds to it.

Reading the tables

How it is counted:

WordingMeaningSource in the BOM view
MeasuredCounted or measured from the designMeasured
A number per somethingThat factor times the count. Change it in FactorRule
Factor you enterThe rule is set and the factor is blank, so the line starts as ! Needs factorRule
You enter itThe line starts as ! Needs quantityManual

When and how:

WordingMeaning
—Applies to every design, with a line whenever the layout has any to count
A design conditionThe entry applies only then. Otherwise it is under Not for this design on the Profile card
WorksInstallation or civil work rather than a supply item
SpareThe allowance follows Spare for discrete consumables, 5 % by default
Off by defaultListed under Switched off on the Profile card, with no line in the BOM

Units are as the application prints them: Nos, set, m, t, m³, LS (lump sum) and MWp. The abbreviations used are MMS (module mounting structure), SMB (string monitoring box), ACCB (AC combiner box), ICR (inverter control room), IDT (inverter duty transformer), MCR (main control room) and USS (unit substation).

PV modules

ItemUnitHow it is countedWhen and how
PV moduleNosMeasured—

Inverters & DC collection

ItemUnitHow it is countedWhen and how
String inverterNosMeasuredString inverter plants
Central inverterNosMeasuredCentral inverter plants
String monitoring box (SMB)NosMeasuredCentral inverter plants
Inverter mounting standNos1 per string inverterString inverter plants

Structure & foundations

ItemUnitHow it is countedWhen and how
MMS table (supply package)NosMeasuredFixed tilt
Module mounting structure steeltFactor you enter, kg per tableFixed tilt · Off by default
Tracker (supply package)setMeasuredTrackers
MMS pileNosMeasuredFixed tilt
MMS pile · tracker posts, when not in the OEM's packageNosMeasuredTrackers · Off by default
Tracker control systemLSMeasuredTrackers
Module mounting bolt setset4 per moduleSpare · Off by default
Module earthing washerNos4 per moduleSpare · Off by default
MMS fastenerstFactor you enter, kg per tableFixed tilt · Off by default

DC cabling & connectors

ItemUnitHow it is countedWhen and how
DC solar cablemMeasured—
DC connector, maleNos1 per stringSpare
DC connector, femaleNos1 per stringSpare
DC connector set with inline fuseset1 per stringString fuses inline, or inline and inside the device · Spare
Y connector setset1 per string pairY harness, with string fuses inside the device or none · Spare
Y connector set with fused armsset1 per string pairY harness, with string fuses inline, or inline and inside the device · Spare
DC trunk cable (SMB → central inverter)mMeasuredCentral inverter plants
Cable gland, single compressionNos1 per conductor endCentral inverter plants · Spare
Cable lug, copperNos1 per conductor endCentral inverter plants · Spare
DC cable lug, bimetallicNos1 per conductor endCentral inverter plants · Spare
HDPE DWC conduit · for DC cablesmMeasuredDC string cable in conduit, buried or above ground
Cable tie · DC cable along the tables and trackersNosMeasuredSpare
Conduit fitting · couplerNosYou enter itDC string cable in conduit, buried or above ground · Spare
Conduit fitting · T jointNosYou enter itDC string cable in conduit, buried or above ground · Spare
Conduit fitting · L jointNosYou enter itDC string cable in conduit, buried or above ground · Spare
Conduit fitting · 3-wayNosYou enter itDC string cable in conduit, buried or above ground · Spare
Conduit fitting · 4-wayNosYou enter itDC string cable in conduit, buried or above ground · Spare
UPVC clamp · above-ground layingNosMeasuredDC string cable above ground · Spare
UPVC clamp · above-ground laying of LV AC cableNosMeasuredAC cable above ground · Spare

LV AC system

ItemUnitHow it is countedWhen and how
AC combiner box (ACCB)NosMeasuredString inverter plants
LV AC cablemMeasuredString inverter plants
Cable glandNos1 per cable endString inverter plants · Spare
Cable lug, bimetallic · source endNos3 per source-end cable endString inverter plants · Spare
Cable lug, aluminium · receiving endNos3 per receiving-end cable endString inverter plants · Spare
LV AC cable · ACCB / central inverter → transformermMeasured—
Cable gland · ACCB / central inverter → transformerNos1 per cable endSpare
Cable lug, bimetallic · ACCB / central inverter → transformer, at the ACCB / inverterNos3 per source-end cable endSpare
Cable lug, aluminium · ACCB / central inverter → transformer, at the transformerNos3 per receiving-end cable endSpare
Ladder cable tray · at the ICRmFactor you enter, per ICR—
Cable tray canopy and support · at the ICRmFactor you enter, per ICR—
Ladder cable tray · for MV cablemMeasuredMV cable on cable tray

MV system

ItemUnitHow it is countedWhen and how
Inverter duty transformerNosMeasured—
MV cablemMeasured—
MV termination kit · at the IDTNos1 per cable end—
MV termination kit · at the MCRNos1 per cable endGrid connection on this site
MV termination kit · at the handover pointNos1 per cable endGrid connection by others
Power transformerNosMeasured—
MV breaker panel (ICOG)Nos1 per ICR—
HT panel · at the MCRNos1 per MCR—
HT panel · at a USSNos1 per USS—
HT feeder panel · for the auxiliary transformerNos1 per MCR—
MV straight-through joint kitNos1 per joint—
Metering yardsetYou enter it—

Earthing & lightning protection

ItemUnitHow it is countedWhen and how
Lightning arrester, ESENosMeasured—
Earth pit · for arrestersNosMeasured—
Earthing strip · for arrestersm50 per arrester—
Earthing cable · for string invertersm15 per string inverterString inverter plants
Earth pit · for string invertersNosMeasuredString inverter plants
Earth pit · for transformers (body)NosMeasured—
Earth pit · for other equipment at the ICRNosMeasured—
Earth pit · for other equipment at the MCRNosMeasured—
Earth pit · for the USSsNosMeasured—
Earth pit · to meet the plant grid targetNosMeasured—
Earth pit · for the fence, poles and other equipmentNosMeasured—
Earthing strip · main earthing ringmMeasured—
Earth pit · for the main earthing ringNosMeasured—
Earthing strip · array meshmMeasured—
Earthing strip · in the cable trenchesmMeasured—
Earthing strip · round the ICRs, MCR and USSsmMeasuredGrid connection on this site
Earthing strip · round the ICRsmMeasuredGrid connection by others
Earthing strip · for the fence, poles and other equipmentmMeasured—
Earthing strip · coppermYou enter it—
Earthing bolt set · array mesh jumpersset2 per jumper or bridgeSpare
Earthing cable lug · for string invertersNos4 per string inverterString inverter plants · Spare
Earthing cable · for central invertersmFactor you enter, per central inverterCentral inverter plants
Earthing cable lug · for central invertersNosFactor you enter, per central inverterCentral inverter plants · Spare
Earthing cable · for SACU, PLC box and SMBmYou enter it—
Earthing cable lug · for SACU, PLC box and SMBNosYou enter itSpare

Communication, SCADA & security

ItemUnitHow it is countedWhen and how
SACU (smart array control unit)Nos1 per ICR blockPower-line communication
CCTV systemsetYou enter it—
Weather monitoring stationset1 at the MCRGrid connection on this site
Weather monitoring station · on siteset1 on siteGrid connection by others
PLC boxNos1 per ICRPower-line communication
RTU panelset1 per ICR—
Modem for remote monitoringsetYou enter it—
RS485 cablemMeasuredRS485 communication
RS485 cable · to the weather stationsm50 per weather station—
CAT-6 cablemYou enter it—
Optical fibre cablemMeasured—
Conduit for communication cablemMeasured—
Conduit for communication cable · for the weather station linksm50 per weather station—
Communication cable termination · RS485Nos8 per cable end (one per core of the 4-pair cable)RS485 communication · Spare
Communication cable termination · RS485, to the weather stationsNos16 per weather station (8 at each end)Spare
Communication cable termination · CAT-6NosYou enter itSpare
Weather monitoring station · module temperature onlyset1 per ICR—

Aux power & lighting

ItemUnitHow it is countedWhen and how
Street light (perimeter)setMeasured—
ACDB panelNos1 per ICR—
Auxiliary transformer · part of the ACCB panelNos1 per ICRString inverter plants
Auxiliary transformer · part of the LT panel / ACDBNos1 per ICRCentral inverter plants
Auxiliary transformer · outdoor, fed by the HT feederNos1 per MCR—
UPSNos1 per ICR—
Equipment-yard light · equipment yardsetFactor you enter, per ICR—
Aux power cable · 3C × 25 mm² AlmYou enter it—
Aux power cable · 4C × 10 mm² CumYou enter it—
Aux power cable · 4C × 16 mm² AlmYou enter it—
Aux power cable · 4C × 35 mm² AlmYou enter it—
Aux power cable · 2C × 4 mm² CumYou enter it—
Aux power cable · 2C × 2.5 mm² CumYou enter it—
Control cable · 19C × 1.5 mm²mYou enter it—
Control cable · NIFPS to ICOG panelmYou enter it—
Control cable · 2C × 1.5 mm²mYou enter it—
Gland for aux and control cable · 2C × 1.5 mm²NosYou enter itSpare
Gland for aux and control cable · 19C × 1.5 mm²NosYou enter itSpare
Gland for aux and control cable · 2C × 2.5 mm²NosYou enter itSpare
Gland for aux and control cable · 2C × 4 mm²NosYou enter itSpare
Gland for aux and control cable · 3C × 25 mm²NosYou enter itSpare
Gland for aux and control cable · 4C × 10 mm²NosYou enter itSpare
Gland for aux and control cable · 4C × 16 mm²NosYou enter itSpare
Lug for aux and control cable · pin, 1.5 mm²NosYou enter itSpare
Lug for aux and control cable · bimetallic pin, 2.5 mm²NosYou enter itSpare
Lug for aux and control cable · bimetallic ring, 2.5 mm²NosYou enter itSpare
Lug for aux and control cable · bimetallic pin, 4 mm²NosYou enter itSpare
Lug for aux and control cable · bimetallic ring, 10 mm²NosYou enter itSpare
Lug for aux and control cable · bimetallic ring, 16 mm²NosYou enter itSpare
Lug for aux and control cable · bimetallic ring, 25 mm²NosYou enter itSpare

Civil works

ItemUnitHow it is countedWhen and how
ICR buildingNosMeasured—
Fence · boundarymMeasured—
Gate · mainNosYou enter it—
Road · perimetermMeasuredWorks · Off by default
Cable trenchmMeasuredWorks · Off by default
Equipment foundation · for string invertersNos1 per string inverterString inverter plants · Works · Off by default
Equipment foundation · for transformersNos1 per transformerWorks · Off by default
Hume pipe · road crossingsNosYou enter it—
MCR buildingNosMeasured—
MCR furniture and air conditioningsetYou enter itGrid connection on this site
MCR wiring and lightingLSYou enter itGrid connection on this site · Works · Off by default
Security cabinsetYou enter it—
Fence · ICR yardm120 per ICR—
Gate · ICR yardNos2 per ICR—
Gravel · ICR yardm³40 per ICR—
Road · internalmYou enter itWorks · Off by default
Road · approachmYou enter itWorks · Off by default
DrainmYou enter itWorks · Off by default
Concrete block for above-ground laying · DC conduit, above groundNosMeasuredDC string cable above ground
Concrete block for above-ground laying · LV AC cable, above groundNosMeasuredAC cable above ground
Concrete block for above-ground laying · DC trunk cable, above groundNosMeasuredDC trunk above ground
Equipment foundation · for central invertersNos1 per central inverterCentral inverter plants · Works · Off by default
Equipment foundation · for SMBsNos1 per SMBCentral inverter plants · Works · Off by default
Equipment foundation · for ACCBsNos1 per ACCBString inverter plants · Works · Off by default
Equipment foundation · for ACDB panelsNos1 per ICRWorks · Off by default
Equipment foundation · for ICOG panelsNos1 per ICRWorks · Off by default
Equipment foundation · for NIFPSNos1 per IDTWorks · Off by default
Equipment foundation · for PLC boxesNos1 per ICRPower-line communication · Works · Off by default
Equipment foundation · for the HT panelNos1 per HT panelWorks · Off by default

Safety & fire

ItemUnitHow it is countedWhen and how
Fire extinguishersetYou enter it—
Fire bucket standsetYou enter it—
First-aid boxNosYou enter it—
Danger and notice boardNosYou enter it—
Safety kitsetYou enter it—
NIFPS (nitrogen injection fire protection)set1 per transformer—

O&M & water

ItemUnitHow it is countedWhen and how
Cleaning robotNosMeasuredOnce a cleaning fleet is sized
Cleaning robot bridgeNosMeasuredOnce a cleaning fleet is sized
Water tank · module cleaningsetYou enter it—
Water tank · MCRsetYou enter itGrid connection on this site
Borewell and RO plantsetYou enter it—

Services

ItemUnitHow it is countedWhen and how
Installation of structure and modulesMWpMeasuredWorks · Off by default
Installation and commissioning, DC sideMWpMeasuredWorks · Off by default
Cable termination works · communication cablesLSYou enter itWorks · Off by default

Mandatory spares

ItemUnitHow it is countedWhen and how
Mandatory sparesLSYou enter it—

What feeds the lines

Most quantities come straight from the layout. These lines also read a design choice, so they are the ones that move when you change it.

Structure

The structure is bought as a package, not in parts.

  • MMS table (supply package) has one line per table type, and its specification prints the table, module, tilt, clearance, wind and finish. For example: "2P × 28 portrait, full table (56 modules); module 2,380 × 1,130 mm, 580 Wp; tilt 8.4°; clearance 0.5 m; wind …; Hot-dip galvanised". It includes the structure, fasteners and module mounting hardware, as per the supplier's design.
  • Tracker (supply package) includes the structure, posts, drive, controller and module mounting hardware, as per the OEM. It is not split into interior and perimeter trackers. Tracker control system is one lump sum.
  • MMS pile needs a pile pattern. See Piles.

DC protection

These lines read the Isc from the PAN file, and Bifacial module and Max series fuse from the Array tab. The design Isc is the module's Isc, plus Bifacial current gain when the module is bifacial.

ItemRule
Inline string fuseString fuse factor × design Isc, then the next listed size
SMB input fuseString fuse factor × strings per input × design Isc, then the next listed size
DC disconnectorDC disconnector factor × the most strings on an SMB × design Isc, then the next listed size
SMB inputsThe most strings on an SMB. With a Y that pairs, the most inputs any SMB uses

The Line card prints the working, such as "String fuse: 1.56 × 15.62 A = 24.3672 A → 25 A (Isc 14.2 A + 10 % bifacial)". Two warnings can appear, and neither changes the status: "The <item> needs <n> A, above the largest size in its list (<largest> A)." and "The <a> A string fuse is above the module's <b> A maximum series fuse." The size lists are BOM settings.

DC harness and string fuses

DC harness and String fuses on the Electrical tab decide the connector lines.

HarnessString fusesConnector lines
One string per inputInline, or inline and inside the deviceDC connector, male and female, plus DC connector set with inline fuse
One string per inputInside the device, or noneDC connector, male and female
YInline, or inline and inside the deviceY connector set with fused arms, one per pair
YInside the device, or noneY connector set, one per pair

Under a Y, a string with a cable of its own keeps its own connectors. The DC solar cable splits: each string's own cable before the Y is at String cable size, and the shared cable after it at Y pair cable size.

Cable laying

The laying choices on the Cables card reach the BOM at the next Generate.

LayingLines it brings
DC string cable in conduit, buried or above groundHDPE DWC conduit · for DC cables, along the route, and five manual conduit fittings
DC string cable, AC cable or DC trunk above groundConcrete block for above-ground laying, the route divided by Concrete block spacing, rounded up
DC string cable above groundUPVC clamp · above-ground laying, one per block
AC cable above groundUPVC clamp · above-ground laying of LV AC cable, each cable divided by the spacing, rounded up
MV cable on trayLadder cable tray · for MV cable, along the MV route

Cable tie · DC cable along the tables and trackers is counted with or without cables, from Cable tie spacing.

Communication and weather stations

ChoiceLines
Power-line, over the AC cableSACU and PLC box, one per ICR
RS485, daisy-chainedRS485 cable, and Communication cable termination · RS485, eight per cable end
A weather stationThe station, 50 m of RS485 cable, 50 m of conduit and 16 terminations
Module sensors at every ICRWeather monitoring station · module temperature only, one per ICR

Each ICR with an MV run has Optical fibre cable as long as that run, so there is no fibre without an MCR, USS or handover point. A chain longer than the limit in Advanced settings puts a remark on the RS485 line.

MV network

The network is radial.

  • MV breaker panel (ICOG): one per ICR, with an incomer per IDT.
  • HT panel · at the MCR: its incomers are the feeders and the USS links. HT panel · at a USS follows the same idea. A handover point has no panel.
  • MV cable: one row per cable schedule row, length × runs.
  • MV straight-through joint kit: runs × one fewer than the number of drums a run takes, from MV cable drum length.
  • Inverter duty transformer: split per rating and winding count, such as "16,000 kVA, 33 kV / 800 V, 5-winding, ONAN, Aluminium windings". See ACCB and transformers.

When a solar park provides the main control room, several of these go. See Grid connection by others.

Earthing

Earthing is measured from the project's earthing design, without opening its window: pits by duty, strips by class, and two bolt sets per jumper or bridge. See Earthing design.

Cleaning fleet and arresters

Cleaning robot and Cleaning robot bridge appear once a fleet is sized in Robotic module cleaning, with one bridge line per kind, standard or supported. Lightning arrester, ESE prints the protection level and mast height in its specification, such as "Level IV, 9 m mast". See Lightning arresters.